SINGLE CORE FIRE RESISTANT

Quick Specification –
– Used in trunking and conduits – places where fire situation may pose a major hazard.
– These cables should be installed in metal conduits.
– Standard – Adapted to EN 50525-3-41
– Technical Data – Voltage rating – 450 to 750 V
– Operating temperature – between -20?C and + 90?C (cable cannot be flexed when temperature is under 0?C)
– Minimum Bending Radius – 8 x Overall diameter
– Stranded plain annealed copper conductor – according to BS EN 60228, class 2
– Mica tape (fire resistant) covered by an extruded layer of cross – LS0H insulating compound
– Sheathed version also available
– Single cable – Circuit Integrity for installation in metal conduits – BS 6387 categories C, W & Z
– Exceeds IEC 60331 – 3 hours at 750?C – when the tested at more than 950?C – equivalent to BS 6387 category C
– Acid Gas Emission – BS EN 50267-2-1, IEC 60754-1
– Smoke Emission – IEC 61034
– Flame Propagation : EN 60332-1, BS EN 50266, EN 60332-3, BS EN 50265
– Insulation colour – 12 ? grey, 09 ? brown, 06 ? green / yellow, 05 ? yellow, 04 ? blue, 03 ? red, 02 ? black, 01 ? green